Intral - Smart Lighting

LED EMERGENCY INVERTER

LED EMERGENCY INVERTER

Inversor de emergência

 Linha:

Imprimir
IP20 - Índice de proteção
50000h - Expectativa de vida útil
Produto Nacional
2 anos de garantia

Características

  • The emergency inverter operates together with the LED current driver of the lamp, transforming the normal LED lamp into an emergency lighting system;
  • It may be used in any LED lamp, observing the output voltage and current of the LED modules (for further information regarding connections, visit www.intral.com.br);
  • Low energy consumption for battery charging: less than 2W;
  • High-capacity NiCd battery: 3000 mAh;
  • It includes circuit breaker for system testing, support and battery chargingLED indicator;
  • It complies with standard NBR 10898 (emergency lighting);
  • Life expectancy higher than 50,000 hours;
  • Installation ambient temperature: 5 to 50°C (41°F to 122°F);
  • Supply voltage: 50/60 Hz.

Observação: Somente utilizar este inversor em lâmpadas que possuam driver externo.

Connections and mechanical data

  • Use rigid 0.5 to 1.5 mm² cables;
  • Strip cables from 8.5 to 9.5 mm;
  • Maximum distance between the Emergency Inverter and LEDs: 2 m;
  • Connect the battery only after installation of the inverter;
  • Never energize the inverter without the battery;
  • Use the battery supplied with the emergency inverter only;
  • Ground the inverter and the lamp;
  • Weight of driver: 0.565 kg.

Dimensions

Table 1

CODE MODEL BATTERY NOMINAL INPUT VOLTAGE  (V) POWER CONSUMPTION(W) TOTAL BATTERY CHARGING TIME (HOURS)
03601 IES-CS6 0600/010IMB NiCd (3000mAh) 127/220 2 24

Table 2

CODE  MODEL OUTPUT VOLTAGE RANGE (Vdc) MAXIMUM OUTPUT POWER (W) OUTPUT CURRENT (mAdc) AUTONOMY* (MINUTES) JUMPER
03601 IES-CS6 0600/010IMB 20 12,0 600 100 sim
45 21,0 465 100 sim
50 24,0 480 90 sim
50 13,5 270 90 não
55 14,5 265 90 não
140 20,5 145 120 não

Connection diagram

Esquema de Ligação 2

Products Line